10/18/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1 As requested per the previous plan review," Please provide for the restroom lighting, exhaust fan, and coordinate with mechanical for fan control".
Ref: 2012 IBC 107.2.1"
It appears the sequence of operation for the restroom exhaust fan was not coordinated between electrical and mechanical. Electrical calls for continuous operation, Mechanical calls for operation during business hours. Please coordinate, and indicate control methods.
Ref: 2012 IBC 107.2.1"