Permit Number: T17CM06986
Parcel: 13705494H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM06986
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
09/13/2017 TPROBAS1 MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Mechanical plans were not included. Please provide.
09/13/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments, Also provide a written response.
#1. Locate and identify the power panels utilized, on the electrical floor plans, and provide complete panel schedules.
#2. Locate and identify all luminaires on the electrical or lighting floor plans, and assign branch circuit and panel designations.
#3. Assign branch circuit and panel designations for electrical outlets, and any other electrical equipment or appliances on the electrical floor plans.
#4. Provide complete compliance with the 2012 IECC for lighting.
Ref: 2012 IBC 107.2.1, 2012 IECC, 2011 NEC.
09/13/2017 LOREN MAKUS ENGINEERING REVIEW Passed
09/13/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A101; Floor Plan: The IBC Section 2902 requires a minimum number of plumbing fixtures. Please indicate plumbing fixture calculations on the drawings, and show the restrooms on the plan.
2. Sheet A101; Floor Plan: A water cooler is indicated in the back of the house area. The City of Tucson requires a high/low drinking fountain, or a single point of use water dispenser (connected directly to plumbing). Please revise.
3. Sheet A101; Floor Plan: The IBC Table 2902.1 requires a service sink to be provided. Please indicate on the plan.
4. Sheet A101; Floor Plan: Signage must be provided and displayed in the back of house area, indicating this area will not be used for storage. Please add to the note in that area that signage is required.
5. Sheet A111; Floor Plan: Please indicate on the plan the locations of walls C2 and C3 (details indicated on this sheet).
6. General: Please provide written responses to all review comments.
09/13/2017 TPROBAS1 WATER REVIEW Reqs Change 1. Water information was not included. Please provide.
09/13/2017 TPROBAS1 PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Plumbing plans were not included. Please provide.
09/13/2017 MARTIN BROWN FIRE REVIEW Approved
10/04/2017 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2017 QJONES1 APPROVAL SHELF Completed
10/04/2017 QJONES1 OUT TO CUSTOMER Completed
10/04/2017 QJONES1 REJECT SHELF Completed