Permit Number: T17CM06960
Parcel: 106070250

Address:
1323 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM06960
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2017 MCASTRO2 ZONING REVIEW Reqs Change Revised DP required.
09/13/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/13/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Structural Calculations; Sheet 23: The steel section indicated in this calculation is a W14x38. Please revise the calculation for this project.
2. Sheet C1.0; Site Plan: Please indicate on the drawing the clear distance from the east side of the canopy to the existing building (two different locations).
3. General: Please provide written responses to all review comments.
09/13/2017 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Passed
09/13/2017 LOREN MAKUS ENGINEERING REVIEW Passed
09/13/2017 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2017 ARUIZ1 OUT TO CUSTOMER Completed