Permit Number: T17CM06850
Parcel: 105102430

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM06850
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2017 MARTIN BROWN FIRE REVIEW Approved
09/21/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/21/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Coordinate the partial waste & vent isometric, B/P3, with the plumbing plans and correct the labels. Reference: Section 107.2.1, IBC 2012.
2. Coordinate the water heater detail, 201/P1, with the architectural plans. Reference: Section 107.2.1, IBC 2012.
3. Where is detail "XXX" located (see plumbing floor plan/P2)?
4. The plumbing floor plan (P1) appears to show the existing 4" building drain originating to the east of the building. From where does it originate and is there an upper terminal cleanout? Reference: Section 107.2.1, IBC 2012.
5. The locations of the existing water meter and gas meter are not legible on the plumbing site diagram; use a portion of the site plan on sheet A1 as the basis for the plumbing site diagram. Show the proposed location of the gravity grease interceptor. Reference: Section 107.2.1, IBC 2012.
6. Correct the label for the 6-burner range on the gas diagram, 1/P2; it is labeled as a hand sink. Reference: Section 107.2.1, IBC 2012.
09/26/2017 QJONES1 ENGINEERING REVIEW Reqs Change
09/26/2017 QJONES1 ZONING REVIEW Reqs Change

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2017 QJONES1 APPROVAL SHELF Completed
09/26/2017 QJONES1 OUT TO CUSTOMER Completed
09/26/2017 QJONES1 REJECT SHELF Completed