Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM06841
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 10/30/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The clubhouse is not a single-family residence. Submit a COMcheck analysis for the addition; include all of the glass being installed in the addition. Show that the new glass complies with the requirements of Table CC402.3, IECC 2012 and that the vertical fenestration does not exceed 30% of the gross above-grade wall area. Reference: Section C401.2.1, IECC 2012. [Second comment: Include the energy calculations for the changes and additions to the building envelope.] [Initial comment: Demonstrate energy code compliance for the additions and alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.] 2. The ventilation calculations were not included on the revised M102 sheet; submit the revised calculations. [Second comment: Revise the ventilation calculations to include all of the rooms ventilated by the air handler (i.e. include the two restrooms and the workout room). Verify the amount of air delivered by the air handler.] [Initial comment: Calculation of the required minimum ventilation for air handlers serving multiple zones requires the calculations described in Sections 403.3.2.3.1 through 403.3.2.3.4, IMC 2012. Reference: Section 403.3.2.3, IMC 2012.] |
| 10/31/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PROJECT: 255 N. Granada Ave. T17CM06841 Building Plan (2nd Review) TRANSMITTAL DATE: October 24, 2017 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/03/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 11/03/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 11/03/2017 | QJONES1 | REJECT SHELF | Completed |