Permit Number: T17CM06841
Parcel: 11619227A

Address:
255 N GRANADA AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM06841
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The specified bottle filler/single drinking fountain may be used to satisfy the requirements of Sections 1109.5 and 2902.1, IBC 2012 provided that cups are provided at an accessible location. [Initial comment: Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for assembly occupancy (e.g. a drinking fountain).]
2. Provide a mixing valve that is listed to ASSE 1070 (see the warning on the specification sheet for the LFL 1170 mixing valve). [Initial comment: Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.]
10/12/2017 ROBERT SHERRY WATER REVIEW Completed
10/12/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Include the energy calculations for the changes and additions to the building envelope. [Initial comment: Demonstrate energy code compliance for the additions and alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.]
2. Revise the ventilation calculations to include all of the rooms ventilated by the air handler (i.e. include the two restrooms and the workout room). Verify the amount of air delivered by the air handler. [Initial comment: Calculation of the required minimum ventilation for air handlers serving multiple zones requires the calculations described in Sections 403.3.2.3.1 through 403.3.2.3.4, IMC 2012. Reference: Section 403.3.2.3, IMC 2012.]
3. The architectural drawing now calls the room a "Club Room/Workout Area" and the mechanical drawing identifies the room as a "Club Room". Coordinate the drawings. [Initial comment: The room identified by the architect as a "Club room" is called out as a "Club room/ Work out area" on the mechanical plan. Clarify the proposed use of the room and adjust the ventilation calculations if required. Reference: Section 403.3, IMC 2012.]
10/23/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Completed
10/24/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 255 N. Granada Ave.
T17CM06841
Building Plan (2nd Review)

TRANSMITTAL DATE: October 24, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2017 QJONES1 APPROVAL SHELF Completed
10/25/2017 QJONES1 OUT TO CUSTOMER Completed
10/25/2017 QJONES1 REJECT SHELF Completed