Permit Number: T17CM06801
Parcel: 13413057D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM06801
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2017 STEVE SHIELDS ZONING REVIEW Approved
09/06/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012.
09/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/06/2017 SSHIELD1 ENGINEERING REVIEW Passed
09/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1; Development Data: The scope of work indicates this is a retail store, but the occupancy is listed as business (B). Please coordinate.
2. Sheet T1; Occupant Load: The occupant load indicated (11) is based on 100 SF/occupant. Since this is a retail use, revise the occupant load using the IBC Table 1004.1.2 with mercantile use.
3. Sheet T1; Applicable Codes: Please include the 2009 ICC/ANSI A117.1 accessibility code to the list.
4. Sheet A1; Alteration Floor Plan: The IBC Section 1014.2(4) does not allow egress to the restroom through the storage room unless requirements under Exception 2 (including 2.1, 2.2, 2.3, and 2.4) are met. Please verify.
5. General: Please provide written responses to all review comments.
09/06/2017 ROBERT SHERRY WATER REVIEW Completed
09/06/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012.
09/06/2017 MARTIN BROWN FIRE REVIEW Approved
09/06/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2017 QJONES1 APPROVAL SHELF Completed
09/13/2017 QJONES1 OUT TO CUSTOMER Completed
09/13/2017 QJONES1 REJECT SHELF Completed