Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T17CM06768
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2017 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Code review indicates 61 occupants in the seating area. This would require 2 exits. Customers may not exit through kitchen. |
| 09/08/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Gas piping below ground requires the use of a factory-applied protective coating. Reference: Section 404.11.2, IFGC 2012. 2. The International Plumbing Code, 2012, is the controlling code for this activity, not the California Plumbing Code or the Uniform Plumbing Code. Reference: Section 101, IBC 2012. 3. Edit the "Mandatory Measures" on sheet P2 and the Plumbing Sheet Notes on sheets P1 and P2 to include only those measures applicable to this activity. Reference: section 107.2.1, IBC 2012. 4. Provide specifications for all plumbing fixtures proposed for this activity. Reference: Sections 303.4 and 402, IPC 2012. 5. Provide automatic faucets for the restroom lavatories that dispense a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 6. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 7. The specified tankless water heater (Paloma PHH-32RDVN) has a capacity of only 4.9 GPM with a 77 degree Fahrenheit rise. Determine if the hot water demand can be satisfied with this water heater. Reference: Section 107.2.1, IBC 2012 and Section 607.1, IPC 2012. 8. Verify that the maximum developed pipe length for the hot water distribution does not exceed 50-feet. Reference: Section 607.2, IPC 2012. 9. The specified tankless water heater is a direct-vent unit: specify the vent sizes, materials and clearances required to install the vents per the manufacturer's instructions. Reference: Section 503.2.3, IFGC 2012. 10. Appliances (e.g. soda dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Note that direct water connections to beverage dispensers at a minimum require the installation of a backflow preventer conforming to ASSE 1022. Reference: Sections 608.1, 608.3 and 608.16.1, IPC 2012. 11. The approved plumbing drawing for the shell building indicates that the existing 4" sanitary building sewer continues to the west to serve the three other suites in the building. The waste plan on sheet P1 shows the sanitary building sewer stopping at the west wall of this suite with new pipe extending to the south. Clarify this arrangement with the building owner and revise the drawing as required. Reference: section 107.2.1, IBC 2012. 12. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012. 13. Show a cleanout for the horizontal drain downstream of the proposed grease interceptor. Reference: Section 708.3.1, IPC 2012. 14. Provide a separate indirect waste pipe for the prep sink to protect against cross-contamination or fouling. Reference: Section 801.2, IPC 2012. 15. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 16. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012. 17. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson. |
| 09/08/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The International Mechanical Code, 2012, is the controlling code for this activity, not the California State Mechanical Code or the Uniform Mechanical Code. Reference: Section 101, IBC 2012. 2. Edit the "Mandatory Measures" and "Sheet Notes" on sheet M1 to include only those measures applicable to this activity. Reference: section 107.2.1, IBC 2012. 3. Verify that the proposed make-up air unit is equipped with a water recycling or reuse system. Reference: Arizona Revised Statues, ARS 45-313. 4. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Section 401.2, IMC 2012. |
| 09/08/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/21/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Sheet Index: White-out may not be used on submittal drawings. Please revise. 2. Sheet A2; Site Plan: Note 5 indicates four patio tables with 16 seats total. It doesn't appear on Sheet A1 (Design Criteria) that the occupants in this area were added to the total occupant load (per the IBC Section 1004.5). Please verify. 3. Sheet A3; Floor Plan: The 13'-4 1/4" long interior wall in the customer seating area depicts a wall type that is not included in the Wall Legend. Please clarify. 4. Sheet A3; Floor Plan: Per the IBC Section 1014.2(4), egress shall not pass through kitchens, storage rooms, closets, or spaces used for similar purposes. With 64 occupants, two exits are required (IBC Section 1015.1), and the requirement of Section 1014.2(4) must be met. Please revise. 5. Sheet A3; Floor Plan: Note 24 indicates a water heater in the northwest corner of the building. Is this supported on the floor, or is a platform provided to suplport the water heater? If a platform, please provide details for the platform, and how that platform is connected to the wall. Include the platform member sizes and how they are supported (wall or roof). Indicate connector sizes and quantities, and provide structural calculations as required. 6. Sheets A4 and A4.1; Elevation D on Sheet A4; Detail A on Sheet A4.1: Please provide vertical grab bars per the ICC/ANSI A117.1 Figure 604.5.1. 7. Sheet A8; Details B and C: Should the stud tables for these two details be the same (both for interior non-rated walls)? Please verify. 8. Sheet A8; Detail I: Please indicate the diagonal bracing size and the connector size and quantity on this detail. 9. General: Please provide calculations on the drawings for the minimum required plumbing fixtures per the IBC Table 2902.1. 10. General: Please provide calculations on the drawings for the minimum required accessible tables/seats per the IBC Section 1108.2.9.1. 11. General: Please provide written responses to all review comments. |
| 10/02/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Lettering or text to small, hard to read. Please increase font to minimum size of 3/32" as required per the City of Tucson Commercial Plan Submittal Requirements. #2. Provide a complete One Line Diagram for the electrical service and associated equipment. Indicate: (a) Available fault current and ratings for the service equipment and panels. (b) Feeder conduit and conductor sizes and types. (c) OCPD's for all panels, and branch circuits. (d) Service size and load calcs. Ref: 2012 IBC 107.2.1, 2011 NEC |
| 10/04/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: 4875 S. Landing Way Suite #180 T17CM06768 Building Plan (1st Review) TRANSMITTAL DATE: October 24 2017 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/27/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 10/27/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 10/27/2017 | QJONES1 | REJECT SHELF | Completed |