Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM06677
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Explain how the connection of the vented fixture drain serving fixture P-1 in the partial waste and vent isometric, B/P3, and connects to a common vent that is already serving two fixtures complies with the requirements of Section 911.3, IPC 2012. |
| 09/15/2017 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/15/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |