Permit Number: T17CM06617
Parcel: 14002010A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM06617
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
09/25/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/26/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G-1 Drawing Index & Sheet A-2: Sheet A-2 is denoted as Dimensioned Floor Plan in the Index but is identified as Reflected Ceiling Plan in the plan set. Verify and coordinate.
2. Sheet A-3: Keynote 3 could not be located on the drawings. Verify
3. Sheet A-3: In the southwest corner, there is a keynote that is not identified by number. Please identify.
4. Sheet A-3: Include on the drawings the location of emergency lights and exit signage.
5. Sheet A-4: Keynote 8 could not be located on the drawings. Verify.
6. Sheet A-6 Building Section A: Keynote 8, existing steel beam, is denoted at the roof drains in 2 locations. Verify and revise.
7. Sheet A-6 Building Section B: Keynote 5, existing roof deck, is denoted at steel columns in 2 locations. Verify and revise.
8. Sheet S1.1 Expansion Bolts in Concrete: Simpson Strong Bolt Report 1771 is no longer valid. Please reference a valid report.
9. Sheet S1.1 Epoxy Bolts and Dowels in Concrete: Hilti HIT-RE 500 SD Report 2322 is no longer valid. Please reference a valid report.
10. General: Provide a Special Inspection Certificate for required special inspections.
11. General: Provide written responses to all comments.