Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM06617
Parcel: 14002010A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM06617
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/29/2017 LOREN MAKUS ENGINEERING REVIEW Approved
08/29/2017 MARTIN BROWN FIRE REVIEW Approved
08/30/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
08/30/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show how the new wall panels and the new doors comply with the requirements of Section C101.4.3, IECC 2012.
08/30/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the calculations used for the natural gas system. The load for 15 unit heaters at 60 MBH is not equal to 1580 MBH. The intent for the future loads is questionable (i.e. why are you noting the installation of a 4" main gas pipe if you are only installing a 3" line?).
2. The gas meter detail on sheet M3.0 is not legible.
08/30/2017 ROBERT SHERRY WATER REVIEW Completed
08/30/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
09/01/2017 STEVE SHIELDS ZONING REVIEW Approved
09/15/2017 KROBLES1 WWM REVIEW Passed