Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM06617
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/29/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/29/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/30/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 08/30/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show how the new wall panels and the new doors comply with the requirements of Section C101.4.3, IECC 2012. |
| 08/30/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the calculations used for the natural gas system. The load for 15 unit heaters at 60 MBH is not equal to 1580 MBH. The intent for the future loads is questionable (i.e. why are you noting the installation of a 4" main gas pipe if you are only installing a 3" line?). 2. The gas meter detail on sheet M3.0 is not legible. |
| 08/30/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/30/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 09/01/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/15/2017 | KROBLES1 | WWM | REVIEW | Passed |