Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM06583
Parcel: 13323093C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM06583
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2017 ANDREW CONNOR ZONING REVIEW Approved
08/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the specifications for the new AC unit (e.g. cooling capacity, SEER, etc).
2. Provide specifications for the proposed kitchen exhaust hood ( note: it must exhaust to the outside).
3. Provide an exhaust fan for the bathroom.
4. The repacement windows require a maximum U-value of 0.40 and a maximum SHGF of 0.25. The window shall be NFRC-certified.
08/28/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. It appears by the pictures provided, that the unit was almost completely stripped of electrical fixtures and wiring. Please provide an electrical floor plan complete with a panel and luminaire schedule. Provide for Arc Fault, GFI, branch circuit protection, smoke detectors, assigned branch circuits , and replaced receptacles with Tamper Resistant, as required per 2011 NEC arts 210, 406, 408. 2012 IBC.
08/28/2017 ACONNOR1 ENGINEERING REVIEW Passed
08/28/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/28/2017 ROBERT SHERRY WATER REVIEW Completed
08/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide specifications for the tub/shower valves (i.e. ASSE listing?).
08/28/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/29/2017 MARTIN BROWN FIRE REVIEW Approved