Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM06583
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 08/28/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the specifications for the new AC unit (e.g. cooling capacity, SEER, etc). 2. Provide specifications for the proposed kitchen exhaust hood ( note: it must exhaust to the outside). 3. Provide an exhaust fan for the bathroom. 4. The repacement windows require a maximum U-value of 0.40 and a maximum SHGF of 0.25. The window shall be NFRC-certified. |
| 08/28/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. It appears by the pictures provided, that the unit was almost completely stripped of electrical fixtures and wiring. Please provide an electrical floor plan complete with a panel and luminaire schedule. Provide for Arc Fault, GFI, branch circuit protection, smoke detectors, assigned branch circuits , and replaced receptacles with Tamper Resistant, as required per 2011 NEC arts 210, 406, 408. 2012 IBC. |
| 08/28/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 08/28/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/28/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/28/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide specifications for the tub/shower valves (i.e. ASSE listing?). |
| 08/28/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/29/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |