| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2018 | EHAMBLI1 | ZONING | REVIEW | Reqs Change | FROM: Elisa Hamblin, AICP Lead Planner PDSD Zoning Review Section PROJECT: T17CM06525 Building Plan Review (3rd Review) 22 E Ventura St TRANSMITTAL DATE: August 24, 2018 DUE DATE: August 30, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans in reference to the revised development package (DP16-0014), but cannot approve them at this time. It appears all Zoning comments from previous reviews have been addressed. 2. COMMENT: Once the plans have been reviewed and approved by the Commercial Plan Reviewers, the building plans can be approved by zoning. 3. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of revised building plans by Zoning. If you have any questions about this transmittal, contact me at (520) 837-4966 or Elisa.Hamblin@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised building plans |
| 09/12/2018 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Chris Anderson, September 10, 2018 BUILDING – COMMERCIAL Include all drawings and other documents that have been stamped “approved” with the reviewer’s signature and review date in the next drawing set submitted for review. Replace only drawings that require correction per these comments. |
| 09/12/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/12/2018 | KROBLES1 | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Chris Anderson, September 10, 2018 PLUMBING – COMMERCIAL It has come to our attention that the civil utilities plan calls out for a backwater valve to be placed on the new sewer service. This will affect the sanitary plumbing for the mezzanine. Per 2012 IPC 715.1 requires that the mezzanine plumbing fixtures shall not discharge through the backwater valve. Please revise the plumbing plans and waste and vent isometric, sheets P1.0, P1.1, P2.0, and any other sheets that are impacted by this change. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 09/19/2018 | QJONES1 | REJECT SHELF | Completed |