Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T17CM06405
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2017 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T17CM06405 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the current code reference on the Inclusive Home Design note #2. SECTIONS - DETAILS: 1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance, and may be a single layer of air-impermeable insulation, or layered with batt insulation for achieving the total required roof R-value. 2. If a vented roof assembly method will be utilized then provide an attic space ventilation calculation and specify size and location of all vents needed to comply with R806.2. PLUMBING PLANS: 1. Show accessibility for servicing the water heater, IPC 502.5.Show hot water pipe with minimum R-3 insulation, N1103.4.2. MECHANICAL PLANS: 1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air or continuous exhaust fan function. 2. Show supply ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, N1103.2.1. Update sheet M1. ELECTRICAL PLANS: 1. Show the location of the panel on the Electrical Plan, E3601.6.2 & E3705.8. 2. Provide a panel schedule showing countertop circuit #18 consistent with the plan, E3602.1 & E3706.1. INTERNATIONAL ENERGY CONSERVATION CODE: 1. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13. Show the "R" values of insulation and the maximum "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1. Update notation on sheet A1. If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/13/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 09/13/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 09/13/2017 | QJONES1 | REJECT SHELF | Completed |