08/23/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Completed COMPLETED IN PREVIOUS WORK FLOW
08/23/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide backflow protection for the tea dispenser (#38); beverage dispensers require the use of a backflow preventer listed to ASSE 1022. Reference: Section 608.16.10, IPC 2012.
2. Where is detail 219 that is referenced in the Plumbing Schedule remarks for kitchen equipment #39?
3. Correct the depiction of the gas supply to the water heater in detail 201: include the sediment trap and place the shut off valve upstream of the sediment trap. Reference: Section 408.4, IFGC 2012.
08/23/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Coordinate the scope of work with regard to the existing AC units. On sheet A3, the contractor is to, "Verify existing mechanical units are in working condition for dining room." The notes on MD-1 call for removal of all the existing mechanical units.
2. Clarify the construction of the wall located behind the proposed Type I hood. Partition detail 2/A3 calls out 2"x 4" studs (including a 2"x 4" pressure treated plate) while the scope of work on the same sheet notes the use of "2x 4 20 GA. metal studs". Section 507.9, IMC 2012 stipulates that the walls within 18" of the hood have a non-combustible structure.
3. Verify that the evaporative cooling section of the specified makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2012 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm).