Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T17CM06198
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/14/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G00.001 Code Information: Please include ANSI A117.1-2009 as a referenced code. 2. Sheet A02.401: Cannot read portions of the drawing from grid lines 4-6 and C-D due to overlapping text. Please revise. 3. Sheet G03.001; stair egress width: The required width indicates 44 inches (each exit) and should be 79(.2)=15.8 inches. Please indicate on this sheet. 4. Sheet G03.001; Door egress width: The required width indicates 32 inches (each door) and should be 79(.15)=11.9 inches. Please indicate on this sheet. 5. Sheet A00.301; Accessible toilet elevation: Please add a verticle grab bar @ the toilet per ANSI A117.1-2009 Figure 604.5.1. 6. Sheet A00.301; Toilet plan 05: The dimension for the distance from the face of the wall to the edge of the lavatory cannot be read. Please revise. 7. Sheet A03.121; Elevation 07: Please add a verticle grab bar @ the toilet per ANSI A117.1-2009 Figure 604.5.1. |
08/14/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/17/2017 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/22/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an automatic faucet for the new restroom lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. The plans call for two separate drinking fountains. Specify which fountain will be mounted for standing access and which will be mounted for wheelchair access. Reference: Section 1109.5.1, IBC 2012 and Section 410.2, IPC 2012 (see also 'Accessibility Notes - Drinking Fountains" on sheet A00.400). |
08/22/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
08/22/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the sequence of operation for the restroom exhaust fan, EF-1, so that all of the air supplied to the restroom will be exhausted (i.e. all of the air supplied to the restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012. |
09/08/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/12/2017 | QJONES1 | APPROVAL SHELF | Completed |
09/12/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
09/12/2017 | QJONES1 | REJECT SHELF | Completed |