Permit Number: T17CM06165
Parcel: 107143510

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM06165
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2017 ANDREW CONNOR ZONING REVIEW Approved
08/10/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
08/10/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please indicate branch circuit and panel designation on the floorplan for lighting and water heater. Provide for water heater disconnecting means.
Ref: 2011 NEC 408, 2012 IBC 107.2.1
08/10/2017 ACONNOR1 ENGINEERING REVIEW Passed
08/10/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please include ANSI A117.1-2009 to the code reference.
2. Provide ADA details which corelate with ANSI A117.1-2009 figures 604.3, 604.5.1 & 604.5.2.
3. As proposed, the configuration of the restrooms do not meet ADA requirements. Please revise to correlate with the requirements of ANSI A117.1-2009 Chapter 6.
4. Provide wall details for the new walls to be constructed. Include in the detail: framing type, size and spacing, wall finish material, anchorage, bracing to structure above including type of bracing material, spacing, type and number of fasteners to be used.
08/10/2017 ROBERT SHERRY WATER REVIEW Reqs Change Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
08/10/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide information to show how the proposed water heater is to be supported from the building structure. Reference: Section 301.2, IPC 2012.
08/10/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/11/2017 JVINCEN1 FIRE REVIEW Approved
08/30/2017 KROBLES1 WWM REVIEW Completed P17WX01942