Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM06144
Parcel: 13314456F

Address:
1200 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM06144
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the new lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Show the location of the required drinking fountains. Reference: Sections 1109.5 and 2902.1, IBC 2012.
08/24/2017 ROBERT SHERRY WATER REVIEW Completed
08/24/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G000 Sheet Index: Sheet CD000 Existing Conditions is denoted on the Sheet Index, Existing Conditions is on Sheet CD00 of submitted drawings. Coordinate.
2. Sheet G000 Code Analysis: Please include ANSI A117.1-2009 as an applicable code.
3. Sheet G001: Update notations and details as necessary to reference ANSI A117.1-2009.
4. Sheet G010 First Floor Life Safety Plan: The Required and Provided Exit width notations are too small. The City of Tucson requires all lettering, upper and lower case, to be a minimum of 3/32" in height. Please enlarge text.
5. Sheet A101 detail 3A, Keynote A06: Include on the drawings a wall detail for the support wall identified in Keynote 06. Include framing member type, size and spacing, anchoring, bracing and wall covering material.
6. Sheet A101: Include on the drawings the required clear floor space and maneuvering clearances at accessible building elements. Reference ANSI A117.1-2009 Chapter 3 & 4.
7. Sheet A101 Detail 4C, Keynote A22: Include on the drawings a wall detail for the new wall identified in Keynote 22. See comment 5 for more information.
8. Sheet A101: Revise Details 4C, 5A, 5B, 5C, 6A & 6B to correlate with ANSI A117.1-2009 Figures 604.3, 604.4, 604.5.1 & 604.5.2. Also, coordinate mounting heights on Sheet G001.
9. Sheet A101: Include on the drawings the Specifications and Mounting Locations of signage for Accessible Restrooms. Reference ANSI A117.1-2009 Section 703
10. General: Provide written responses to all comments.
09/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed