Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM06137
Parcel: 13409013B

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T17CM06137
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2017 JVINCEN1 FIRE REVIEW Approved
08/11/2017 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
08/15/2017 ANDREW CONNOR ZONING REVIEW Approved
08/16/2017 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS
08/16/2017 LOREN MAKUS ENGINEERING REVIEW Passed
08/30/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets T-1 and A-3: Please darken the text on these sheets.
2. Sheet A-6 (Details 2 and 4); Structural Calculations (Pages 3 and 11): The structural calculations indicate the masonry walls are to be solid grouted, while the details indicate to grout the reinforced cells. Please clarify.
3. Sheet A-6 (Detail 4); Structural calculations (Pages 15 and 16): The calculations indicate top and bottom foundation reinforcing at the masonry wall, while the detail indicates bottom foundation reinforcing only. Please clarify.
4. General: Please provide written responses to all review comments.
09/07/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2017 KROBLES1 OUT TO CUSTOMER Completed