Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM06078
Parcel: 11310026B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM06078
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2017 MARTIN BROWN FIRE REVIEW Approved
08/24/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Ref: Plan Sheet PV-05.
#1. Add clarification or more details on the plans as to the total scope of work associated with the modification to the existing service equipment required to accommodate the PV installation.
#2. Indicate or provide for a complete grounding electrode system for the service equipment. If utilizing the existing system, verify compliance with 250.24A.
#3. The conductors shown between the last inverter and the junction box are indicated as 2-#12 and 1 #10 AWG. Are these conductors sized for the combined output of all the paralleled inverters? Please clarify.
#4. Indicate conduit and conductor sizes and types for the feeders from the junction boxes to the PV load center.
#5. Clarify what the panels marked as 1, 6, and 7, and the 6 dots between inverters signify.
#6. Provide the available fault current value at service and verify that the associated equipment is rated accordingly.
#7. Ref: Plan Sheet PV-06.
Under "Branch Circuit Information". Justify the conductor rating for #12 AWG to be 25 AMPS at 60 C terminals. See 110.14C, and 310.15B.
Ref: 2012 IBC sec. 107.2.1, 2011 NEC .
Dan Santa Cruz
COMMERCIAL ELECTRICAL PLAN REVIEW, City of Tucson.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2017 ARUIZ1 OUT TO CUSTOMER Completed