Permit Number: T17CM05856
Parcel: 12310001A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM05856
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed
09/18/2017 MARTIN BROWN FIRE REVIEW Passed
09/22/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Identify electrical equipment as new or existing on the one-line diagrams and schedules.
#2. Clarify the difference between the bold solid lines and the lighter solid lines and the same with the slashed lines shown on the one-line diagrams. This was not clarified on the symbols plan.
#3. The Project Summary description states 'S4E-901, SWGR-1B, ATS-24 as new equipment. Please provide a new equipment schedule or indicate as requested per comment #1.
Ref: 2012 IBC 107.2.1, 2011 NEC.