Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM05856
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/18/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Passed | |
09/18/2017 | MARTIN BROWN | FIRE | REVIEW | Passed | |
09/22/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Identify electrical equipment as new or existing on the one-line diagrams and schedules. #2. Clarify the difference between the bold solid lines and the lighter solid lines and the same with the slashed lines shown on the one-line diagrams. This was not clarified on the symbols plan. #3. The Project Summary description states 'S4E-901, SWGR-1B, ATS-24 as new equipment. Please provide a new equipment schedule or indicate as requested per comment #1. Ref: 2012 IBC 107.2.1, 2011 NEC. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/10/2017 | QJONES1 | APPROVAL SHELF | Completed |
10/10/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
10/10/2017 | QJONES1 | REJECT SHELF | Completed |