Permit Number: T17CM05788
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05788
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-1: The 2 Break Room Elevation callouts are both denoted as 10/A-7. Also, elevation 10 is not included on Sheet A-7. Please revise.
2. Sheet A-1: The Coffee Bar has an elevation callout which is a Sink Base Cabinet Section. Please revise to reference the correct elevation.
3. Sheet A-4 Enlarged Floor Plan: The Elevator Lobby Elevation Callouts 1 & 4/A-6 appear to be reversed. Verify and revise as necessary.
4. Sheet A-4 Enlarged RCP: Keyed Notes 3 & 5 could not be located on the drawing. Verify and revise.
5. Sheet A-6 Detail 9: Soffit detail indicates 2x framing. Verify and indicate on the drawings that the 2x is of material permitted to be used with Type 1A construction. Reference IBC 602.2 & 603
6. Sheet A-6 Elevation 6: Indicate on the drawing the mounting height of the 18" vertical grab bar. Reference ANSI A117.1-2009 Figure 604.5.1
7. Sheet A-8 Detail 14: At the cross brace, indicate on the plans the type, size & number of fasteners to be used.
8. General: Provide written responses to all comments.
09/01/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Panel 14DBP is fed with a 200 amp OCPD in panel 14DP. This is in violation of NEC art. 408.36 and art. 240.4.

Ref: 2012 IBC 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2017 QJONES1 APPROVAL SHELF Completed
09/06/2017 QJONES1 OUT TO CUSTOMER Completed
09/06/2017 QJONES1 REJECT SHELF Completed