Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05788
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-1: The 2 Break Room Elevation callouts are both denoted as 10/A-7. Also, elevation 10 is not included on Sheet A-7. Please revise. 2. Sheet A-1: The Coffee Bar has an elevation callout which is a Sink Base Cabinet Section. Please revise to reference the correct elevation. 3. Sheet A-4 Enlarged Floor Plan: The Elevator Lobby Elevation Callouts 1 & 4/A-6 appear to be reversed. Verify and revise as necessary. 4. Sheet A-4 Enlarged RCP: Keyed Notes 3 & 5 could not be located on the drawing. Verify and revise. 5. Sheet A-6 Detail 9: Soffit detail indicates 2x framing. Verify and indicate on the drawings that the 2x is of material permitted to be used with Type 1A construction. Reference IBC 602.2 & 603 6. Sheet A-6 Elevation 6: Indicate on the drawing the mounting height of the 18" vertical grab bar. Reference ANSI A117.1-2009 Figure 604.5.1 7. Sheet A-8 Detail 14: At the cross brace, indicate on the plans the type, size & number of fasteners to be used. 8. General: Provide written responses to all comments. |
| 09/01/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Panel 14DBP is fed with a 200 amp OCPD in panel 14DP. This is in violation of NEC art. 408.36 and art. 240.4. Ref: 2012 IBC 107.2.1, 2011 NEC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/06/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 09/06/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 09/06/2017 | QJONES1 | REJECT SHELF | Completed |