Permit Number: T17CM05787
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05787
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-1: Detail 6/A-8 is called out at multiple locations where a partition abuts a column. Detail 6/A-8 is for partitions at a mullion. Verify and revise to reference correct detail.
2. Sheet A-2: Keyed Notes 5, 6 & 7 could not be located on the drawing.
3. Sheet A-4 Elevator Lobby Elevation & Sheet A-6: Elevations 1 & 4 Sheet A-6 appear to be reversed. Verify and revise as necessary.
4. Sheet A-4 Enlarged Reflected Ceiling Plan: Keyed Note 3 could not be located on the drawing.
5. Sheet A-5 Restroom Elevation Keyed Notes: Keyed Notes 13, 14, & 15 could not be located on the drawing.
6. Sheet A-6 Elevations 5, 6, 7, & 8: These elevations are denoted as being applicable for restroom 904. Should this be Restroom 908?
7. Sheet A-6 Detail 9: Soffit detail indicates 2x framing. Verify and indicate on the drawings that the 2x is of material permitted to be used with Type 1A construction. Reference IBC 602.2 & 603
8. Sheet A-6 Elevation 6: Indicate on the drawing the mounting height of the 18" vertical grab bar. Reference ANSI A117.1-2009 Figure 604.5.1
9. Sheet A-8 Detail 14: At the cross brace, indicate on the plans the type, size & number of fasteners to be used.
10. General: Provide written responses for all comments.
09/01/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Plan Sheet E-4 shows the special systems for the third floor. Please clarify.
#2. Panel 9DPB is fed with a 200 amp OCPD in panel 9DP. This is in violation of NEC art. 408.36 and art. 240.4.
Ref: 2012 IBC 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2017 QJONES1 APPROVAL SHELF Completed
09/06/2017 QJONES1 OUT TO CUSTOMER Completed
09/06/2017 QJONES1 REJECT SHELF Completed