Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05787
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-1: Detail 6/A-8 is called out at multiple locations where a partition abuts a column. Detail 6/A-8 is for partitions at a mullion. Verify and revise to reference correct detail. 2. Sheet A-2: Keyed Notes 5, 6 & 7 could not be located on the drawing. 3. Sheet A-4 Elevator Lobby Elevation & Sheet A-6: Elevations 1 & 4 Sheet A-6 appear to be reversed. Verify and revise as necessary. 4. Sheet A-4 Enlarged Reflected Ceiling Plan: Keyed Note 3 could not be located on the drawing. 5. Sheet A-5 Restroom Elevation Keyed Notes: Keyed Notes 13, 14, & 15 could not be located on the drawing. 6. Sheet A-6 Elevations 5, 6, 7, & 8: These elevations are denoted as being applicable for restroom 904. Should this be Restroom 908? 7. Sheet A-6 Detail 9: Soffit detail indicates 2x framing. Verify and indicate on the drawings that the 2x is of material permitted to be used with Type 1A construction. Reference IBC 602.2 & 603 8. Sheet A-6 Elevation 6: Indicate on the drawing the mounting height of the 18" vertical grab bar. Reference ANSI A117.1-2009 Figure 604.5.1 9. Sheet A-8 Detail 14: At the cross brace, indicate on the plans the type, size & number of fasteners to be used. 10. General: Provide written responses for all comments. |
| 09/01/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Plan Sheet E-4 shows the special systems for the third floor. Please clarify. #2. Panel 9DPB is fed with a 200 amp OCPD in panel 9DP. This is in violation of NEC art. 408.36 and art. 240.4. Ref: 2012 IBC 107.2.1, 2011 NEC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/06/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 09/06/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 09/06/2017 | QJONES1 | REJECT SHELF | Completed |