Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM05786
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05786
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-1 Keynote 14, Details 1 & 5 Sheet A-7: The low wall identified in 1/A-7 by Keynote A is called out in Detail 5/A-7 as a 2x4 wall. Verify and indicate on the plans the 2x4 framing is of material permitted to be used with Type 1A construction. Reference IBC Section 602.2 and IBC Section 603.
2. Sheet A-1 Keynote 17: Keynote 17, ceiling mounted projector references detail 15/A-7. This detail is for a sink base cabinet. Please revise to reference the correct detail.
3. Sheet A-1 Enlarged Reception Desk Plan & Detail 1/A-7: Elevation 3 is denoted in 2 locations. Please revise.
4. Sheet A-1 Breakroom Elevations 9/A-7 & 10/A-7 Elevations on Sheet A-7 are reversed. Please revise.
5. Sheet A-2: In the elevator lobby a sconce light fixture is identified by Keynote 4 as a sconce light fixture. Verify and revise as necessary.
6. Sheet A-2: keynotes 5, 6, &7 could not be located on the drawing.
7. Sheet A-4 Keynote 7, Detail 9/A-6: Soffit detail indicates 2x framing. Verify and indicate on the plans the 2x framing is of material permitted to be used with Type 1A construction. Reference IBC Section 602.2 and IBC Section 603
8. Sheet A-5 Enlarged Restroom & Sheet A-6 Elevations: Elevations 5, 6, 7, & 8 on Sheet A-6 is for Restroom 304. Should these elevations be for Restroom 308? Verify and revise as necessary.
9. Sheet A-8 Detail 14: At the cross brace, indicate on the plans the type, size and number of fasteners to be used.
10. General: Provide written responses to all comments.
08/31/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2017 QJONES1 APPROVAL SHELF Completed
09/06/2017 QJONES1 OUT TO CUSTOMER Completed
09/06/2017 QJONES1 REJECT SHELF Completed