Permit Number: T17CM05769
Parcel: 140122190

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05769
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2017 MMORENO1 ZONING REVIEW Approved
10/09/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/09/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/09/2017 MMORENO1 ENGINEERING REVIEW Passed
10/09/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S5 (Detail 3); Structural Calculations (Sheet B.4): Roof joist RJ1 called out as (2) 2x8 at 24" o.c., while Detail 3 indicates 2x6 at 24" o.c. Please verify.
2. Sheet S5 (Detail 23); Structural Calculations (Sheet B.4): Roof beam RB1 (on east wall) called out as 5 1/8" x 12" GLB in the calculations, while the detail indicates 3-2x12. Is the RB1 indicated on the calculations correct? Please verify.
3. Sheet S6 (Canopy Layout); Structural Calculations (Sheet C.1): The calculations indicate the canopy joists are 1x3x1/8 at 6'-6" o.c.at canopies 'A', 'B', and 'D'. The joists are spaced further apart than 6'-6" at these three canopies. Please verify.
4. General: Please provide written responses to all review comments.
10/09/2017 ROBERT SHERRY WATER REVIEW Completed
10/09/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/09/2017 MARTIN BROWN FIRE REVIEW Approved
10/09/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/13/2017 ARUIZ1 WWM REVIEW Passed