Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05768
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/01/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/02/2017 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/04/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A001: Building Classification and Plumbing Calculations denotes the area as 5,632 square feet but the Egress Requirements has the area denoted as 6,140 square feet. Please clarify. 2. Sheet A001: Occupant load used for egress requirements (52) is not consistent with the occupant load used for the plumbing calculations (47). Please clarify. 3. Sheet A001: Regarding the above comments; if this inconsistency is due to unoccupied space being deducted, please note such on the drawings. 4. Sheet A002 Details 4 & 5: Please remove reference to Sheet A601 as this sheet is not included in the plan set. 5. Sheet S1 Expansion Bolts in Concrete: Simpson Strong Bolt Report 1771 is no longer valid. Please reference a valid report. 6. Sheet S1 Epoxy Bolts in Concrete: Hilti HIT-RE 500 SD Report 2322 is no longer valid. Please reference a valid report. 7. Structural Calculations: Please provide a Keyplan for the beams and foundations. 8. Structural Calculations: Please include calculations for Foundation F-1 and Beam B-3. 9. Structural Calculations: Calculations included 2 columns of different sizes, each identified as Column C-1. Please clarify. 10. Sheet S1: Please denote the required special inspections. Reference IBC Chapter 17 11. Provide Special Inspection Certificate. 12. General: Provide written responses to all comments. |
| 08/09/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/09/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the type of drinking fountain being installed in vestibule 109; the unit is specified as a dual height fountain but shown as a single drinking fountain on sheet P2.1. Reference: Section 107.2.1, IBC 2012. 2. Individual shower valves are required to be listed to ASSE 1016; the specified valve is listed to ASSE 1069, 1070, and 1017. Reference: Section 424.3, IPC 2012. |
| 08/10/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Specify the maximum acceptable NFRC-certified U-factors and Solar Heat Gain Coefficients (SHGC) for the new windows. Reference: Section C103.2, IECC 2012. 2. Revise the heating and cooling load calculations for HP-2 using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson (104Fdb/66Fwb cooling; 32F heating). 3. Provide the results of the heating and cooling load calculations that were used to determine the capacities of the PTAC units and HP-1. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012. 4. Provide the seasonal energy efficiency rating (SEER) for HP-1. Reference: Section C403.2.3, IECC 2012. 5. Show how outside air will be supplied to HP-1. Reference: Section 107.2.1, IBC 2012. |
| 08/22/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 08/25/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comment. Also provide a written response. Provide details on the electrical plans for the exhaust fan controls in the unit restrooms. Ref; 2012 IBC 107.2.1, 2011 NEC |