Permit Number: T17CM05754
Parcel: 140122210

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05754
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2017 ANDREW CONNOR ZONING REVIEW Approved
07/27/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/27/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. #1.Please provide a complete panel schedule that correlates with the branch circuits for the relocated or new electrical equipment. Also designate a branch circuit and panel for the power poles and coolers.
#2. No registrant seal on the power plan.
Ref: 2012 IBC 107.2.1, 2011 NEC art. 408
07/27/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/27/2017 ROBERT SHERRY WATER REVIEW Completed
07/27/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/27/2017 MARTIN BROWN FIRE REVIEW Approved
07/27/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/09/2017 KROBLES1 WWM REVIEW Passed