Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05629
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/24/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
07/24/2017 | TPROBAS1 | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
07/24/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
07/24/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
07/24/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A01; Building Code Summary: The required plumbing fixtures should include a high/low drinking fountain or a single point of use water dispenser. Please indicate in this summary, and indicate on the floor plan. 2. Sheet A12; Plan: The plan is indicated under the drawing as 'RCP'. Please revise. 3. Sheet A12; Detail D3: Please indicate the length of the #4 dowels, and the length of the dowel embedment into the new slab. 4. General: Please provide written responses to all review comments. |
07/24/2017 | TPROBAS1 | WATER | REVIEW | Completed | |
07/24/2017 | TPROBAS1 | PLUMBING-COMMERCIAL | REVIEW | Completed | |
07/24/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/25/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |