Permit Number: T17CM05611
Parcel: 13348128F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05611
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2017 ANDREW CONNOR ZONING REVIEW Approved
07/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/28/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/28/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/28/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1.0; Code Review: Please revise the square footage on the drawing, and coordinate the numbers shown. Include the outdoor area square footage with the building square footage for the total.
2. Sheet G1.0; Code Review (Plumbing Requirements): Since this is not a change of use, the existing restrooms will be acceptable. On the Code Review, remove the calculations and indicate with a note that restroom fixtures are existing, and there is no new work in them under this permit.
3. General: Please provide written responses to all review comments.
07/28/2017 ROBERT SHERRY WATER REVIEW Completed
07/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/28/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/31/2017 MARTIN BROWN FIRE REVIEW Approved