Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05611
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/28/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/28/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/28/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 07/28/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/28/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 07/28/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/28/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/28/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G1.0; Code Review: Please revise the square footage on the drawing, and coordinate the numbers shown. Include the outdoor area square footage with the building square footage for the total. 2. Sheet G1.0; Code Review (Plumbing Requirements): Since this is not a change of use, the existing restrooms will be acceptable. On the Code Review, remove the calculations and indicate with a note that restroom fixtures are existing, and there is no new work in them under this permit. 3. General: Please provide written responses to all review comments. |
| 07/31/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |