Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM05603
Parcel: 117140860

Address:
40 E 14TH ST #03

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM05603
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
11/21/2017 FRODRIG2 BUILDING-COMMERCIAL REVIEW Reqs Change T17CM05601 through 5608 - PLAN REVIEW COMMENTS – 3rd review
Reviewer: Chris Anderson, November 21, 2017
BUILDING – COMMERCIAL
PER PREVIOUS COMMENT: On sheet G1.1 provide handrail extensions for the ramps that extend a minimum of 12” from ramp edge in the direction of travel. Handrail extensions 90-degrees to the direction of travel do not comply with Code. Revise the plan and details to comply with Code. Ref. ICC/ANSI A117.1-2009 505.10.
PER PREVIOUS COMMENT: Gates keynote 01 on sheet G1.2 indicate that the gates will be keyed from both sides. This does not comply with 2012 IBC 1008.1.9 that requires egress doors to be readily openable from the egress side without the use of a key of special knowledge or effort.
PER PREVIOUS COMMENT: Per ICC/ANSI A117.1-2009 1004.12.2.1, a parallel approach is acceptable for kitchen sinks as long as the 48” clear floor space is centered on the sink bowl. This appears not to be the case for units 1, 2, 6, 7 and 8. Revise the plans to comply.
PER PREVIOUS COMMENT: New bathroom lavatories for all units are shown to be 3’-0” above the floor from what appears to be the centerline of the fixture. ICC/ANSI A117.1-2009 1004.11.3.2.1.1 requires that the maximum height of the lavatory rim be 34” above the floor. Revise to comply.
PER PREVIOUS COMMENT: Carbon monoxide alarms are required outside each separate sleeping area in the immediate vicinity of bedrooms. Add this note to the drawings. Ref. 2012 IBC 908.7.