Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05572
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/21/2017 | ANDREW CONNOR | ZONING | REVIEW | Reqs Change | Submittal and approval of the following is required prior to review of building plans: SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS). Over the counter review of development package would be available. |
07/21/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
07/21/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
07/21/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
07/24/2017 | TPROBAS1 | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
07/24/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide the power requirements for the new AC unit, and correlate with the panel schedule and load calcs. Be advised, there are no spaces available on panel 'B'. Also panel 'B' is a 120/240 Volt panel. #2. Provide a description or cut sheet for the proposed new luminaire. Ref: 2012 IBC sec 107.2.1, 2011 NEC |
07/24/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/24/2017 | TPROBAS1 | PLUMBING-COMMERCIAL | REVIEW | Passed | |
07/28/2017 | TPROBAS1 | WATER | REVIEW | Completed |