Permit Number: T17CM05572
Parcel: 12603167A

Address:
665 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05572
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2017 ANDREW CONNOR ZONING REVIEW Reqs Change Submittal and approval of the following is required prior to review of building plans: SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS).
Over the counter review of development package would be available.
07/21/2017 LOREN MAKUS ENGINEERING REVIEW Passed
07/21/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/21/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/24/2017 TPROBAS1 MECHANICAL-COMMERCIAL REVIEW Completed
07/24/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response. #1. Provide the power requirements for the new AC unit, and correlate with the panel schedule and load calcs. Be advised, there are no spaces available on panel 'B'. Also panel 'B' is a 120/240 Volt panel.
#2. Provide a description or cut sheet for the proposed new luminaire.
Ref: 2012 IBC sec 107.2.1, 2011 NEC
07/24/2017 MARTIN BROWN FIRE REVIEW Approved
07/24/2017 TPROBAS1 PLUMBING-COMMERCIAL REVIEW Passed
07/28/2017 TPROBAS1 WATER REVIEW Completed