Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM05553
Parcel: 11619154C

Address:
450 N FREEWAY

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM05553
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2017 MARTIN BROWN FIRE REVIEW Reqs Change Cover sheet indicates a fire alarm system in buildings B & C. Alarms are not required for these buildings. Please verify intent.
07/27/2017 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T17CM05553
Building Plan Review (1st Review)
450 N Freeway (U-haul International)

TRANSMITTAL DATE: July 27, 2017

DUE DATE: August 21, 2017

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans for compliance with the approved development package. While the building footprint is consistent with the approved DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the Commercial Plans reviewers have approved the building plans.


2. COMMENT: Assure that an approved and signed copy of the DP16-0108 is included with the next submittal of the building plans as reference. (Zoning was able to do a comparison the building plans with the DP plan have been approved by all PDSD reviewers and were available. The DP has outstanding fees due and has yet to be picked up by the applicant.)


3. COMMENT: Zoning will review the building plans on the next submittal to assure that any revisions made to the building plans do not affect zoning requirements.

4. COMMENT: A hold on issuance of a permit for the building plans until the fees for the DP have been paid and the plans retrieved by the applicant. Keep in mind that approved plans have an expiration date and a re-submittal of the DP may be necessary if the DP is not retrieved by the applicant with a specified time period. Contact PDSD for the for more information on the DP expiration date.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building plans and copy of the approved DP as reference.
08/08/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
Submit exterior lighting lumen calculations showing compliance with the 2012 City of Tucson/Pima County Outdoor Lighting Code Table 401.1. Select a commercial lighting option from the Table and provide lumen calculations in tabular form for the site area shown on sheet E2.0. The lumen total (shielded + unshielded) and the unshielded lumen total must equal or be less than the allowable lumens for each category per the selected option. The site photometric plan shown on sheet E1.1 is not in a format that indicates compliance with the OLC.
Light pole base detail 2/E2.0 states “verify requirements with structural engineer provided by general contractor.” There is no light pole detail in the structural drawings. Submit structural calculations for the light pole base. If the SE includes a light pole base detail different from 2/E2.0, eliminate the detail on the electrical sheet.
The interior and exterior light fixture schedules on sheet E4.2 appear to indicate that all the exterior light fixtures (SA, F1, F2, F1E) have a color temperature of 4,000K. The 2012 Outdoor Lighting Code 402.1 limits the color temperature for all exterior lighting at 3,500K. Please revise the schedules to comply.
08/08/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Indicate the water meter locations and size, backflow preventer location and size, routing of site water and sewer and gas to building on the site plan, or submit a civil site plan for reference showing all these items.
Please confirm that the lavatory faucet scheduled in the Fixture Connection Schedule, sheet P0.2, will deliver no more than 0.25 gallon per metering cycle. Ref. City of Tucson amendment to the 2012 IPC.
08/08/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM05553 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, August 4, 2017
BUILDING – COMMERCIAL
To Energy Code Analysis, sheet T1.1, add glazed fenestration requirements; Fixed Fenestration maximum U value = 0.50, Operable Fenestration maximum U value = 0.65, Entry Doors maximum U-value = 0.83, and maximum SHGC = 0.25. Ref. 2012 IECC Table C402.3.
A single loading dock is shown on the architectural site plan, sheet A1.1 and enlarged plan sheet A10.7. No drain at the bottom of the loading ramp is shown on the enlarged plan and details on sheet A10.10 seem to indicate three different pit draining techniques. Which detail on sheet A10.10 will be used for this facility? Please cross out the two details that are not applicable and reference the proposed drain method detail on the enlarged plan. Also, show the drain pipe routing to daylight on the architectural site plan. Ref. 2012 IBC A107.2.1.
The exterior warehouse light fixture shown on sheet A10.12 appears to have a color temperature rating of 4000K. The maximum color temperature ratings for any exterior fixture is 3500K. Ref. City of Tucson/Pima County Outdoor Lighting Code 402.1.
A geotechnical report is referenced in the General Structural Notes and in foundation plan notes. Please submit the referenced report for review
Provide structural calculations sealed by the structural engineer of record so that information shown on the structural drawings can be verified. Please make sure that designations for footings, posts, beams, etc. in the calculations are clearly keyed to the structural plans and schedules so that the plans reviewer can easily compare them to each other.
08/08/2017 FRODRIG2 WATER REVIEW Reqs Change WATER – COMMERCIAL
Indicate the water meter locations and size, backflow preventer location and size, routing of site water and sewer and gas to building on the site plan, or submit a civil site plan for reference showing all these items.
08/08/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
Submit heating and cooling calculations summary sheet for each proposed heating and cooling unit to justify selections. Per 2012 IECC C403.2.2 “the output capacity of heating and cooling equipment and systems shall not exceed the loads calculated om accordance with Section C403.2.1.” Be aware, also, that the summer outside air design db temperature is 104-degrees F with the indoor air wb design temperature 66-degrees F. The winter db design temperature is 35-degrees F. The heating and cooling load calculations and the selection of heating and cooling equipment must be based on these air temperatures. Ref. Pima County amendment to the 2012 IECC.
08/22/2017 LOREN MAKUS ENGINEERING REVIEW Approved
08/23/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2017 ARUIZ1 OUT TO CUSTOMER Completed