08/02/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM05511 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, August 1, 2017
BUILDING – COMMERCIAL
The description for 1-hour demising wall A1 on sheet A1.1 calls for 5/8” Type X drywall on tenant side. Submit a tested assembly showing that drywall on one side of a stud partition will achieve a 1-hour fire rating.
08/02/2017 JVINCEN1 FIRE REVIEW Approved
08/02/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
The plumbing sheets must be sealed by an Arizona registrant. Ref. A.R.S. 32-144(3).
Where will the new bathroom plumbing be connected to existing plumbing? The demolition plan gives no indication that there is existing plumbing near the new restroom location. Indicate location for existing water and sewer, routing of new plumbing and connection points on an enlarged area plan. Show sizes of existing plumbing lines. Ref. 2012 IPC 106.3.1.
Verify that faucet for new lavatory is automatic and will dispense no more than 0.25 gallon per metering cycle. Ref. City of Tucson amendment to 2012 IPC.
08/02/2017 FRODRIG2 WWM REVIEW Approved PER CHRIS ANDERSON AT PIMA COUNTY.
08/02/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
The electrical sheets must be sealed by an Arizona registrant. Ref. A.R.S. 32-144(3).
Submit interior lighting power calculations per 2012 IECC C405.
08/02/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
The mechanical sheets must be sealed by an Arizona registrant. Ref. A.R.S. 32-144(3).
Submit outside air calculations for this space and show how the required ventilation will be achieved. Ref. 2012 IMC 106.3.1 and 403.2.
Show how the bathroom exhaust will be controlled so that bathroom maintains negative pressure. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent air stream. Ref. 2012 IMC 403.2.1(4).
No supply air is shown for the bathroom. Should door 4 be undercut?
Keynote 6 on sheet M1 refers to outside air and return air ducts, however none are shown on the mechanical plan. Please revise the plan to show all existing and new ducts, outlets, inlets, cfm’s etc. pertinent to this tenant space. Ref. 2012 IMC 106.3.1