Permit Number: T17CM05511
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05511
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/20/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide exhaust for the dressing rooms per Table 403.3, IMC 2012. Reference: Section 403.3, IMC 2012.
07/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/20/2017 ENEWCOM1 FIRE REVIEW Needs Review
07/20/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
07/20/2017 ROBERT SHERRY WATER REVIEW Completed
07/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
07/31/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/31/2017 ANDREW CONNOR ZONING REVIEW Approved
07/31/2017 AHINES2 WWM REVIEW Needs Review