Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM05494
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Assign a branch circuit as well as a panel designation for all electrical equipment, receptacles, and lighting. #2. Provide a complete panel schedule, include load calcs. Ref; 2012 IBC sec, 107.2.1, 2011 NEC art 408. City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/16/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |