Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM05426
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2017 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | It appears the sprinkler increase was taken for allowable area. This would preclude the ability to install a NFPA 13R system. Per 2012 IBC, section 504.1, it would have to be a full 13 system. Please revise fire sprinkler notes on sheet T1.0. Also, it is our contention that because this is a commercial building, a commercial hood, with a fire suppression system, is required. Please confirm with the mechanical reviewer. |
| 07/27/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet T1: Please include calculations for required accessible units. Reference IBC Chapter 11 2. Sheet A1.0: Window Type 1 is denoted at bathroom 4; verify window is to be installed in that location. 3. Sheet A1.0 Bedroom 12 & Bathroom 6: Bedroom window type 7 is less than 24 inches from the vertical edge of the door from bathroom 6. Should this be considered a hazardous location and be provided with safety glazing? Reference IBC 2406.4.2 4. Sheet A1.0 Bedrooms 16 & 17: Windows near entry door is less than 24 inches from the vertical edge of the entry door. Should this be considered a hazardous location and be provided with safety glazing? Reference IBC 2406.4.2 5. Sheet A1.0 Occupant Load and Egress: Sheet T1.0 denotes an occupant load of 30; egress path from west portion of building indicates an occupant load of 30 with 15 occupants using the north exit door out of the open space and 15 occupants using the south exit door out of the open space. Also, there is an additional 11 occupants using the east exit door. Please clarify. 6. Sheet A1.0 & Door Schedule Sheet A5.0: Doors separating Open Space and Dwelling units is denoted as Type 5 which is identified in the Door Schedule Sheet A5.0 as being ADA Unit Bathroom. This door also indicates hardware Type 04 Privacy Lockset. Please verify door and hardware type as these doors are part of a means of egress. 7. Sheet A3.0 Reflected Ceiling Plan: Keynote 5 could not be located on the plans. 8. Sheet A6.0 Detail 1: Grab bar is misidentified as a wall mounted lavatory by Keynote 3. Please revise. 9. Sheet A6.0 Detail 8: Mop sink is misidentified as an electric water heater by Keynote 13. Please revise. 10. Sheet A6.0 Detail 8: The water heater is misidentified as a shower base by Keynote 12. Please revise. 11. Sheet A6.0 Detail 8: The wall surface is misidentified as a door by Keynote 16. Please revise. 12. Sheet A7.0: Include details of kitchen cabinets and appliances illustrating compliance in regards to allowable reach ranges, height and location of controls etc. Reference ANSI A117.1-2009 13. Sheet S1.1 Epoxy: Hilti HIT-RE 500 SD Report 2322 is no longer valid. Please reference a current report. 14. Provide a Special Inspection Certificate. 15. Provide written responses to all comments. |
| 07/31/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/01/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a floor drain (minimum size shall be 3") for the central clothes washing facility per Section 412.4, IPC 2012. 2. For the use of PEX tubing, provide a sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2012. 3. Verify that the vent for the kitchen sink will be able to rise vertically to at least 6" above the flood rim of the sink prior to running horizontally. Reference: Section 905.4, IPC 2012. 4. Coordinate the required slope for the building drain. The waste calculation on sheet P3.1 calls for a ΒΌ" slope per 12" but the waste and vent schematic on sheet P2.1 calls for a 1/8" slope per 12". Reference; Section 107.2.1, IBC 2012. |
| 08/01/2017 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Tucson Water limits a 1" meter to a maximum demand of 37.5 GPM. Verify that Tucson water will allow the use of "bathroom groups" for the demand calculations and provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for this project. |
| 08/03/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a minimum exhaust flow rate of 100 CFM for the range hood in the kitchen (assuming intermittent operation). Reference: Section 403.3, IMC 2012. 2. Verify that the materials installed in the return air plenum around the supply ducts conform to Section 602.2.1, IMC 2012. 3. Provide energy code compliance calculations for the modifications to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and NFRC-rated U-factors of the fenestration components, along with the R-values of the insulation and the NFRC-rated SHGC for the fenestration. Reference: Sections R101.4.3, R101.5, R103.2, and R401.2, International Energy Conservation Code 2012. |
| 08/14/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |