Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM05371
Parcel: 12616303A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05371
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/17/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/17/2017 ROBERT SHERRY WATER REVIEW Passed
07/18/2017 STEVE SHIELDS ZONING REVIEW Approved
07/19/2017 MARTIN BROWN FIRE REVIEW Approved
07/28/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet a0.7; Project Data: Please include the parking structures P1 and P2 in the project data and include information as required.
2. Sheet a2.4; Garage Plan: Please indicate P1 and P2 on this plan for clarity.
3. Sheet a2.4; Garage Plan: Please indicate the existing walls in P2 with demolition keynote 200.
4. Sheet a3.4; Key Notes: In note 333, please add a note to reference sheet s2.0 for footings.
5. Sheet a3.4; Key Notes: Note 331 indicates an area of refuge. Please explain the IBC requirement for this.
6. General: Please provide a valuation (labor and materials) for P1 and P2 separately.
7. General: Please provide an occupant load for P1 and P2, separately and indicate on the drawings.
8. General: Please provide written responses to all review comments.
07/28/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/03/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. It appears that there is exterior lighting shown on the site plan per clouded areas delta 3, which was not shown on previous plan submittal. Re- submit for this change for all the buildings to reflect the exterior lighting. This lighting including the parking garage lighting will need to comply with the Tucson/Pima County Outdoor Lighting Code. Please provide complete compliance as outlined per section 104. The Outdoor Lighting Code can be downloaded from www.tucsonaz.gov/pdsd.
#2. Provide for a Grounding Electrode System at P1 as required per NEC art 250.32.
Ref: 2012 IBC 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.
08/04/2017 ARUIZ1 ENGINEERING REVIEW Needs Review