Permit Number: T17CM05335
Parcel: 128041740

Review Status: Completed

Review Details: WALK THRU - RES

Permit Number - T17CM05335
Review Name: WALK THRU - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2017 TWEIDEM1 BUILDING-RESIDENTIAL REVIEW Reqs Change T17CM05335
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects
comments to be addressed. In order to facilitate a shorter back check time, we request
that you please provide revised plans and calculations, highlighting any changes, along
with a written response to each of the noted items indicating action taken.
SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy
conservation and electrical. All code references are to the 2012 International Residential
Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised
Statutes. All features were checked only to the extent allowed by the submittals
provided. All portions of this project are assumed to meet or will meet other
departmental requirements, conditions and concerns before permit approval.
DIAGRAMS / CALCULATIONS
1. Show the sum of the main and backfeed breakers not exceeding 120% of the busbar
(and conductor) rating, NEC 690.64 & 705.12 (D). The distribution panel bus and
feeder (extended bus) conductor requires a rating for receiving electrical power from
two sources. Show the panel rating and a minimum 117 AMP feeder rating when
placed between source breakers of 100A & 40A. (117A conductor x 120% equal or
greater than 100A + 40A), or move the backfeed breaker to the service panel.
If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/12/2017 TOM WEIDEMAN ENGINEERING REVIEW Passed