07/14/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a registrant seal on all the Electrical plan sheets.
#2. Why is there a PV disconnect between the service equipment and the transfer switch ?
#3. Show the OCPD rating protecting the generator output feeders.
#4. Include the sub-panel and show how it is being utilized in this system.
Ref: 2012 IBC 107.2.1, 2011 NEC