Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM05333
Parcel: 14042030A

Address:
6970 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM05333
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2017 MARTIN BROWN FIRE REVIEW Approved
07/12/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/12/2017 ANDREW CONNOR ZONING REVIEW Approved
07/14/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/14/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Completed
07/14/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a registrant seal on all the Electrical plan sheets.
#2. Why is there a PV disconnect between the service equipment and the transfer switch ?
#3. Show the OCPD rating protecting the generator output feeders.
#4. Include the sub-panel and show how it is being utilized in this system.
Ref: 2012 IBC 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
07/24/2017 KROBLES1 OUT TO CUSTOMER Completed