Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM05333
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/12/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/12/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
07/12/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
07/14/2017 | TPROBAS1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
07/14/2017 | TPROBAS1 | BUILDING-COMMERCIAL | REVIEW | Completed | |
07/14/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a registrant seal on all the Electrical plan sheets. #2. Why is there a PV disconnect between the service equipment and the transfer switch ? #3. Show the OCPD rating protecting the generator output feeders. #4. Include the sub-panel and show how it is being utilized in this system. Ref: 2012 IBC 107.2.1, 2011 NEC |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/24/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |