Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM05305
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2017 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 07/11/2017 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 07/12/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/12/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please provide a calculation for the connection of the roof deck to the purlins, and indicate that on a drawing. 2. Please indicate on a drawing the gauge of the roof deck. 3. Please indicate on the drawing the total required depth of the pier foundation. 4. The drawing for the foundation indicates a 2' diameter pier, then a dimension at the bottom of the pier indicates 2'-6". Please coordinate. 5. Please provide written responses to all review comments. |
| 07/12/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/20/2017 | ARUIZ1 | OUT TO CUSTOMER | Completed |