Permit Number: T17CM05305
Parcel: 12315158C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM05305
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/11/2017 ANDREW CONNOR ZONING REVIEW Approved
07/12/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/12/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please provide a calculation for the connection of the roof deck to the purlins, and indicate that on a drawing.
2. Please indicate on a drawing the gauge of the roof deck.
3. Please indicate on the drawing the total required depth of the pier foundation.
4. The drawing for the foundation indicates a 2' diameter pier, then a dimension at the bottom of the pier indicates 2'-6". Please coordinate.
5. Please provide written responses to all review comments.
07/12/2017 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/20/2017 ARUIZ1 OUT TO CUSTOMER Completed