Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/17/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/17/2017 ROBERT SHERRY WATER REVIEW Completed
07/17/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The revised specification for the lavatory faucet calls for a cycle time of 7.5-seconds. For accesibility, the minimum cycle time shall last at least 10-seconds. Reference: Section 606.4, ICC/ANSI A117.1-09. [Initial comment: Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds per cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.]
07/18/2017 ARUIZ1 WWM REVIEW Needs Review