Permit Number: T17CM05296
Parcel: 133165790

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05296
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2017 ANDREW CONNOR ZONING REVIEW Approved
07/11/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if there is no motion in the restroom). Reference: Section 403.2.1 (4), IMC 2012.
07/11/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/11/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/11/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Completed
07/11/2017 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of both the water service meter and the reduced pressure backflow preventer assembly. Provide the total water demand served by the watr meter. Reference: Section 107.2.1, IBC 2012.
07/11/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds per cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. The wall cleanout upstream of the water closet should be 4", not 3" as shown on 2/M1.1 or 2" as shown on 4/M2.1. Reference: Section 708.7, IPC 2012.
07/11/2017 MARTIN BROWN FIRE REVIEW Approved
07/11/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
07/17/2017 KROBLES1 WWM REVIEW Needs Review