Permit Number: T17CM05294
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05294
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
07/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
08/01/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/01/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Registrants expiration date shall be included on all Architectural Sheets. Reference Arizona Board of Registration.
2. Sheet A0.00 Plumbing Fixtures: Separate facilities are required for each sex per IBC 2902.2. Provide an additional restroom within the tenant space or reference male and female facilities which are available for public use and indicate travel distance.
3. Sheet A1.00: At barricade and mall concourse, indicate the minimum width to be maintained.
4. Sheet A2.00: Wall type 1E is denoted between the unisex restroom and accessible fitting room; wall type 1E is not included in the wall legend. Verify wall type designation and revise as necessary.
5. Sheet A0.00; Project Data (Accessibility Requirements): Please add the 2009 Edition of ANSI A117.1 to the code reference.
6. Sheet S1.00: Clark Dietrich Light Gauge Metal Studs Report 2457 is no longer valid. Please reference a current report.
7. General: Provide written responses to all comments.