Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM05294
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM05294
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2017 ANDREW CONNOR ZONING REVIEW Approved
07/11/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if there no motion in the room). Reference: Section 403.2.1 (4), IMC 2012.
2. Specify how the pressurized exhaust duct within the return air plenum is to be sealed. Reference: Section 603.9, IMC 2012.
07/11/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/11/2017 ACONNOR1 ENGINEERING REVIEW Passed
07/11/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Needs Review
07/11/2017 ROBERT SHERRY WATER REVIEW Completed
07/11/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water for the public restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Correct the water heater detailto show the installation of a vacuum relief rather than a vacuum breaker. Reference: Section 504.2, IPC 2012.
07/11/2017 MARTIN BROWN FIRE REVIEW Approved
07/11/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/12/2017 GERRY KOZIOL WWM REVIEW Completed